학교내 일렬형 배치 급식시설의 미세먼지 저감방안에 관한 연구

A Study on the Reduction of PM10 in a Line-Type School Meal Service Facility
  • 차대오; 
  • 황정하

초록

In this study, single day PM10 concentrations were measured for a Line-type school meal service facility. PM10 concentrations generated by cooking and other student activities were measured and analyzed. The analysis results were used as an input for a simulation to examine the existing exhaust hood and Air Handling Unit (AHU) were in operation [EXT], and for other cases in which alternative measures were initiated for PM10 reduction in the kitchen and cafeteria, such as installation of an additional exhaust hood [ALT-1], cafeteria zoning [ALT-2], and installation of a waste heat recovery ventilation unit [ALT-3]. The simulation results of PM10 concentration distributions for each reduction measure were compared with the results of [EXT]. It was observed that the PM10 reduction efficiency of [ALT-1] was 1.4% in both kitchen and cafeteria, 17.8% in the kitchen and 23.9% in the cafeteria for [ALT-2], and 49.3% in the kitchen and 61.9% in the cafeteria for [ALT-3].

키워드

급식시설; 실내 미세먼지; 조리실 배기후드; 식당 조닝; 환기시스템; School meal service facility; Indoor particle matter; Kitchen exhaust hood; Cafeteria zoning; Ventilation system