R-134a 터보냉동기 응축기의 무세정 수처리 약품 효과 연구

A Study on the Effect of Non-Clean Water Treatment Chemicals for R-134a Turbo-Chiller Condensers
  • 정다운; 
  • 김만회

초록

This paper presents an experimental study on the main management factors of the condenser contamination such as fouling and corrosion for the R-134a turbo-chiller to save energy, reduce corrosion rates, and reduce maintenance costs through the application of condenser non-cleaning water treatment chemical. The series of experiment is conducted using combining oxidative microbial sterilizers, non-oxidizing microbial sterilizers, and anti-corrosion agents. The leaving temperature difference and corrosion rates for three different combination of chemicals are collected and analyzed. The experimental results show that the cost reduction (4,066,000 Won/year) of the disinfectant (FT-830) can be achieved by adding the oxidative disinfectant (NaOCl) and the non-oxidizing disinfectant (NX-1116). The LTD value is maintained at 1.9℃, and the corrosion rates of copper and carbon steel specimens are 0.07 mpy and 1.61 mpy, respectively.

키워드

출구온도차; 에너지소비지수; 수처리 약품; 시편; 연간부식율; 터보냉동기; Leaving temperature difference; Energy Consuming Index; Water treatment chemicals; Specimen; mpy; Turbo-chiller
제목
R-134a 터보냉동기 응축기의 무세정 수처리 약품 효과 연구
제목 (타언어)
A Study on the Effect of Non-Clean Water Treatment Chemicals for R-134a Turbo-Chiller Condensers
저자
정다운; 김만회
발행일
2022-08
유형
Y
저널명
한국수소및신에너지학회논문집
권
33
호
4
페이지
437 ~ 445